The machine at a glance
Terms used on this page
- PLC (programmable logic controller)
- The industrial computer that runs the machine: it reads the sensors, decides what happens next, and drives the motors and valves.
- HMI (operator screen)
- The touchscreen operators use to run the machine, see its status and respond to alarms.
- I/O (inputs and outputs)
- The electrical connections to sensors, switches, lights and valves. Fieldbus I/O is a block of these connections that talks to the PLC over a network cable instead of a separate wire for every signal.
- EtherNet/IP
- The industrial Ethernet standard that Allen-Bradley equipment uses to talk to each other. It runs on ordinary Ethernet cable.
- Studio 5000
- Rockwell’s software for programming Allen-Bradley PLCs and PanelView 5000 screens. Your maintenance team uses it to view and change the program.
- Stratix 4300 and FactoryTalk Remote Access
- Rockwell’s remote-access router and the Rockwell online service it connects to. Together they let ADC support the machine without travelling.
- OPC UA
- A widely used standard for sharing machine data with plant systems such as MES, SCADA or a historian.
When ADC uses Allen-Bradley
Most machines ADC builds use PC-based control: instead of a PLC, a rugged industrial PC runs ADC’s own control software. It is ADC’s standard because it costs less and gives ADC more flexibility. ADC builds on Allen-Bradley PLCs instead when:
- your site does not accept an industrial PC as a machine controller;
- your site standardises on Allen-Bradley, so your maintenance team can support the machine with the tools and training it already has;
- ADC is supporting or modifying an existing Allen-Bradley machine.
- PC-based control (ADC standard)Industrial PC with real-time Linux. Lower hardware and programming cost.
- Allen-Bradley (on request)CompactLogix PLC and PanelView 5000. Your team’s existing tools and training. Usually an upcharge.
Controller
For Allen-Bradley machines, ADC’s standard PLC is the CompactLogix 5380 series. Models in the series differ in how many devices and motors they can handle. ADC picks the one that fits your machine and names it in the quote. If your site standard calls for a different Allen-Bradley PLC (for example a ControlLogix), ADC will use it.
For small systems with limited I/O, ADC also has experience with Allen-Bradley Micro800 PLCs. They cost less than a CompactLogix. Note that they are programmed with Rockwell’s Connected Components Workbench rather than Studio 5000, so your maintenance team would need that software as well.
Programming
ADC writes the PLC program in structured text, one of the standard PLC programming languages (IEC 61131-3). It reads like ordinary written code rather than a ladder diagram, which suits the calculations and sequences in ADC’s machines. ADC works in Rockwell’s Studio 5000 Logix Designer, the same software your maintenance team uses for its other Allen-Bradley equipment, and hands over the complete program with the machine.
Operator screens (HMI)
For systems using Allen-Bradley controllers, ADC’s standard operator touchscreen is the Allen-Bradley PanelView 5000 series. ADC designs its screens in Studio 5000 View Designer, part of the same Studio 5000 software as the PLC program. The screens read their values straight from the PLC program, so the two cannot drift out of step, and alarms written into the PLC program appear on the screen automatically.
PanelView Plus 7 (FactoryTalk View ME) or OptixPanel (FactoryTalk Optix) terminals can be used instead at your request, at additional cost. OptixPanels include their own online remote-access feature. If you do not want it, ADC leaves it switched off, and remote support works as described below.
Fieldbus I/O
The machine’s sensors, switches and valves connect to fieldbus I/O blocks, which pass their signals to the PLC over EtherNet/IP. ADC’s standard I/O brands are Murr Elektronik and WAGO. Both are well-established industrial brands, widely available, and the same I/O ADC uses on its PC-based machines, so ADC’s designs and spare parts carry over.
If your site keeps Allen-Bradley I/O on the shelf and wants the machine to match its spare parts, ADC uses Rockwell’s current I/O lines instead:
- ArmorBlock 5000 (on the machine)
- Sealed I/O blocks that mount on the machine frame, outside the control panel, rated for washdown.
- FLEX 5000 or Compact 5000 I/O (in the control panel)
- DIN-rail I/O modules for inside the panel. Compact 5000 I/O is the companion family to the CompactLogix 5380.
ADC does not recommend the original FLEX I/O (1794) for new machines. Rockwell has been discontinuing it module by module, several with no direct replacement, so spare parts will get harder to find. If your site has another I/O standard, ADC follows it.
Cost
An Allen-Bradley machine usually costs more than the same machine with ADC’s PC-based control. Allen-Bradley components cost more, and programming takes longer. ADC can quote both options side by side so you can weigh the difference.
How Allen-Bradley remote access works
Remote support lets an ADC engineer look at the machine, diagnose a problem and change the program from ADC’s office, without a site visit. It is optional. For Allen-Bradley machines, ADC uses Rockwell’s own remote-access system: a Stratix 4300 router in the control panel, connected to Rockwell’s FactoryTalk Remote Access online service. If your site already uses FactoryTalk Remote Access, the machine can join your existing account alongside your other Rockwell equipment. Otherwise ADC can hold it in ADC’s account (see Who owns the router’s account, below).
For sites that do not want Rockwell’s service, ADC can instead fit a small gateway running Tailscale, the secure remote-access service ADC uses on its PC-based machines. The security guide for IT describes it.
The parts
- Stratix 4300 Remote Access Router (in the control panel)
- A small router that mounts on the rail inside the control panel. On one side it plugs into the machine’s network (PLC, touchscreens, drives). On the other side is its uplink, its connection to the Internet: a network cable to your plant, Wi-Fi, or a cellular (mobile phone network) connection on the wireless models. ADC selects the model for the machine.
- FactoryTalk Remote Access (Rockwell’s cloud service)
- Rockwell’s online service, run on Microsoft’s Azure cloud. Each customer has an account, which Rockwell calls a domain. It lists the routers, the people allowed to use them, what each person may reach, and a log of every connection.
- Remote access tools (on the ADC engineer’s computer)
- Rockwell’s software on the engineer’s laptop. The engineer signs in, connects to the router, and then works in Studio 5000 as if standing next to the machine.
What happens during a support session
- Router connects outThe Stratix 4300 keeps an encrypted connection out to Rockwell. Nothing can connect in.
- Engineer signs inA Rockwell account with multi-factor authentication.
- Permission checkedRockwell’s service checks the engineer is allowed on this router.
- Machine onlyStudio 5000 reaches the PLC and touchscreen, never your plant network. The session is logged.
- The router keeps an encrypted connection open, going out to Rockwell’s servers. Nothing on the Internet can open a connection in to the machine. (For your IT team: one outgoing TCP port, 443, or 80 or 5935 if your policy prefers; Rockwell recommends blocking all incoming traffic.)
- An ADC engineer signs in with their Rockwell account. Rockwell requires multi-factor authentication (a code from a phone app, as well as a password).
- The service checks the engineer’s permissions in the router’s account, then connects them to the router through Rockwell’s relay servers. The channel is end-to-end encrypted, and Rockwell states that relay servers store no data.
- Once connected, the engineer’s laptop can reach the machine’s network behind the router, as if plugged in at the panel. Rules in the account can narrow this to specific devices, such as the PLC and touchscreens. ADC works only on the machine’s network. The router never gives access to your plant network.
- The session is recorded in the domain’s connection log: who connected, to what, and for how long.
How it differs from Tailscale or a traditional VPN
Your IT team may compare FactoryTalk Remote Access with two other approaches. Tailscale is the secure remote-access service ADC uses on its PC-based machines. A traditional VPN is the kind of remote connection your IT team may already run for employees, extended to ADC.
| FactoryTalk Remote Access (Allen-Bradley machines) | Tailscale (ADC’s PC-based machines) | Traditional VPN into your network | |
|---|---|---|---|
| Who runs the service | Rockwell (hosted on Microsoft Azure) | Tailscale (coordination service); the tailnet can be yours | Your IT team |
| Hardware at the machine | Stratix 4300 router | Tailscale on the PC-based controller, or a small gateway | None. Access lands on your network. |
| Connection direction | Outbound only from the router | Outbound only | Inbound to your VPN gateway |
| Traffic path | Relayed through Rockwell’s relay servers, end-to-end encrypted | Direct device-to-device where possible (WireGuard); relays only as fallback, which cannot decrypt | Through your VPN gateway |
| Firewall needs | One outgoing TCP port (443, 80 or 5935) | Outgoing TCP 443, plus UDP for direct connections | An inbound port and VPN gateway you operate |
| How ADC engineers sign in | FactoryTalk Hub accounts with Rockwell multi-factor authentication | ADC’s Microsoft SSO with MFA, or your identity provider | Accounts in your directory, under your policies |
| What ADC can reach | The machine network behind the router, narrowed by rules in the account | Controller and machine network only, narrowed by tailnet access rules | Whatever your VPN policy allows. Segmentation is yours to set. |
| Who controls access | The account owner: you or ADC | Your tailnet admins (recommended) or ADC | Your IT team |
| Audit trail | Connection log in the account | Tailscale audit and flow logs | Your VPN logs |
| Licensing | Rockwell subscription, sized by concurrent connections | Tailscale plan | Your existing VPN |
| Best fit | Sites already on Rockwell remote access; Allen-Bradley lines | PC-based machines; sites without a Rockwell standard | Sites whose policy requires all vendor access through their own VPN |
In short: FactoryTalk Remote Access and Tailscale both connect out from the machine and never open an inbound port, and both can limit ADC to the machine network. They differ in who runs the service and how engineers sign in. FactoryTalk Remote Access relays sessions through Rockwell, using Rockwell accounts. Tailscale connects directly and can use your own sign-in. A traditional VPN puts ADC on your network, so isolating the machine depends entirely on your VPN rules.
Who owns the router’s account
- ADC’s accountADC registers the router and pays for its connections. Simplest for you.
- Your accountYour IT team decides who connects, and can remove ADC at any time.
Every Stratix 4300 router is registered to one FactoryTalk Remote Access account (a domain, in Rockwell’s terms). Whoever owns that account controls who can connect to the machine. ADC offers two options:
- ADC’s account (standard for machines ADC supports)
- ADC registers the router to its own account and pays for the connections its engineers use. Nothing is needed from you beyond an Internet connection for the router. ADC can invite your engineers so they can connect too. This is simplest for you, but ADC, not your IT team, decides which ADC engineers can connect.
- Your account (recommended when your IT team wants control)
- The router is registered to your existing FactoryTalk Remote Access account, alongside your other Rockwell equipment. Your administrators grant and revoke ADC’s access, and ADC’s connections use your subscription.
Setting it up
| Item | In ADC’s account | In your account |
|---|---|---|
| Account and subscription | ADC’s account and subscription | Your existing FactoryTalk Remote Access account and subscription. It must have a connection free when ADC connects, because connections cannot be shared between organizations. |
| Router registration | ADC registers it | ADC registers it into your domain, with access you grant |
| ADC engineer accounts | Already in place | You invite the named ADC engineers to your organization. Each uses a myRockwellAutomation account on their ADC email address, with multi-factor authentication. |
| Permissions | ADC grants its engineers access to this router | You grant ADC’s group permission on this router, including network (VPN) access. Inviting a user does not give device access by itself. |
| Your engineers | Invited by ADC on request | Already in your organization |
| Access rules in the account | ADC limits access to the machine’s devices (PLC, PanelView, drives) | You set them, from the address list ADC provides |
| Internet connection for the router | You provide it | You provide it |
| Removing ADC’s access | Ask ADC, or unplug the router’s Internet connection | Remove ADC’s permissions in your account at any time |
The router’s Internet connection is the same in both options: a network cable, guest or restricted Wi-Fi, or a cellular SIM card for a cellular model. For your IT team: it needs one outgoing TCP port (443 preferred; 80 or 5935 as alternatives) and DNS. Nothing incoming is needed, and all incoming traffic should stay blocked.
Sources
- Rockwell Automation: Stratix 4300 Remote Access Router
- Rockwell Automation: FactoryTalk Remote Access
- Rockwell Automation: FactoryTalk Remote Access security architecture
- FactoryTalk Remote Access help: Best practices (firewall ports)
- FactoryTalk Remote Access help: Domain user permissions
- FactoryTalk Remote Access help: Invite users to an organization
- FactoryTalk Remote Access release notes (multi-factor authentication)
Security
What is different about a PLC
A PLC is not a general-purpose computer. It runs Rockwell’s controller firmware on an embedded real-time operating system, not Windows or Linux. That changes how it is secured: there is no endpoint-security software (such as CrowdStrike) to install on it, and it is patched by updating its firmware when Rockwell publishes a security advisory, not through routine operating system updates. The Stratix 4300 router is the other device on the machine to review, and How Allen-Bradley remote access works (above) describes how it connects.
Is a PLC secure by itself?
No. PLCs were designed to be reliable, not to defend themselves, and Allen-Bradley PLCs are actively targeted. In April 2026 the FBI, CISA, NSA and other US agencies warned that attackers were breaking into internet-exposed Allen-Bradley CompactLogix and Micro850 PLCs, and also Schneider Electric and Siemens PLCs. The attackers changed and deleted PLC programs, altered what operators saw on their screens, and disabled shutdown and alarm logic, so machines could run in unsafe conditions without warning anyone. Most of these PLCs were simply reachable from the Internet.
Choosing Allen-Bradley does not make a machine secure, and neither does choosing PC-based control. What protects a machine is how it is connected and looked after.
What ADC does, and what to keep doing
- Never on the InternetThe PLC is never reachable from the Internet. Remote support goes out through the Stratix router only.
- Passwords changedDefault passwords on the router, and on any other device that has one, are replaced before shipment.
- Firmware kept currentApply Rockwell security updates during planned maintenance. ADC can help.
- Verified backupsKeep an offline copy of the program ADC hands over, and compare against it after any change.
- Keep the machine’s network separate from your plant network, and allow only the connections the machine needs. If the PLC shares data with plant systems, your IT team should firewall that link like any other.
- Remote access goes through an account with named users, multi-factor authentication and a connection log. Review who has access, and remove people who no longer need it.
- Watch for unexpected changes. Studio 5000 can compare the running program with your backup, and the remote-access log shows who connected and when.
- Ask ADC before connecting the machine to anything new, such as another network, a modem or a vendor’s remote-access box.
Common sense applies. No control system is secure by itself, whatever the brand. A machine stays secure when it is kept off the Internet, only the right people can reach it, it is updated, it is backed up, and someone notices when it changes. ADC builds every machine that way and will work through it with your IT team. Keeping it that way after handover is a shared job.